§ 30-263. Minimum separation.
No septic tank subsurface absorption system shall be constructed, nor shall any permit for such construction be issued, if:
(1)
Any portion of the system is located less than 50 feet from any water well or pump suction line.
(2)
Any portion of the system is less than ten feet from a property line.
(3)
Any portion of the system is located less than ten feet from a foundation wall.
(4)
Any portion of the system is less than ten feet from a pressurized waterline.
(Code 1988, § 30-302; Ord. No. O-46-05, § 1, 6-2-2005)